New Part E Building Regulations- Noise Control Solutions for Floors, Walls and CeilingsNew Part E Building Regulations- Noise Control Solutions for Floors, Walls and CeilingsNew Part E Building Regulations- Noise Control Solutions for Floors, Walls and CeilingsNew Part E Building Regulations- Noise Control Solutions for Floors, Walls and CeilingsNew Part E Building Regulations- Noise Control Solutions for Floors, Walls and Ceilings

Soundproofing Solutions to Meet New Part E Building Regulations

Custom Audio Designs carries out Part E Sound Testing. Call for Details.

INTERNAL WALLS / PARTITIONS

UNDER PART E:-

  • The internal wall requirement for the new Part E Regulations is 40 RwdB.
  • An internal wall is defined as a wall between a bedroom or room containing a W.C. and other rooms.
  • There is no Part E requirement for an internal wall that contains a door.
  • Internal walls are not subject to pre-completion testing.
  • With internal wall applications there is no Ctradjusting factor required under Part E.
SOLUTION NO.APPLICATIONPERFORMANCE
Type 1.1Metal Stud53 RwdB
Type 1.2Timber Stud43 RwdB

SEPARATING WALLS

UNDER PART E:-

  • The separating wall requirement for the new Part E Regulations is 45 DnT,w+ CtrdB for New Build.
  • The separating wall requirement for the new Part E Regulations is 43 DnT,w+ CtrdB for Refurbishment
  • A separating wall is defined as a wall separating one dwelling from another.
  • There is no Part E requirement for an internal wall that contains a door.
  • Internal walls are not subject to pre-completion testing.
  • With internal wall applications there is no Ctradjusting factor required under Part E.
SOLUTION NO.APPLICATIONPERFORMANCE
Type 2.1Double Metal Stud57 RwdB+Ctr(66 RwdB)
Type 2.2Independant Metal C Stud53 RwdB+Ctr(58 RwdB)
Type 2.3Double Timber Stud52 RwdB+Ctr(62 RwdB)
Type 2.470mm Acoustic Stud51 RwdB+Ctr(61 RwdB)
Type 2.5Independant Metal C Stud50 RwdB+Ctr(58 RwdB)
Type 2.670mm Acoustic Stud49 RwdB+Ctr(61 RwdB)
Type 2.7Timber Stud48 RwdB+Ctr(55 RwdB)
Type 2.8100mm Brick48 RwdB+Ctr(56 RwdB)

SEPARATING FLOOR SYSTEMS

UNDER PART E:-

  • The Airborne sound requirements for separating floors under the new Part E Regulations is 45 DnT,w+ CtrdB for New Build.
  • The Airborne sound requirements for separating floors under the new Part E Regulations is 43 DnT,w+ CtrdB for Refurbishment
  • The   Impact sound requirements for separating floors under the new Part E Regulations is 62 L'nT,wdB for New Build.
  • The   Impact sound requirements for separating floors under the new Part E Regulations is 64 L'nT,wdB for Refurbishment
  • A separating floor is defined as a floor separating one dwelling from another.
  • Part E requirements for floors is subject to both impact and airborne regulations.
  • Separating Floors are subject to pre-completion testing.
  • With separating floors the Ctradjusting factor is included under Part E.
  • With Impact sound measurements remember the lower the figure the higher the performance.
SOLUTION NO.APPLICATIONPERFORMANCE
Type 3.1Timber Joist Floor60 RwdB+Ctr(70 RwdB)
46 LnwdB
Type 3.2Timber Joist Floor54 RwdB+Ctr(63 RwdB)
56 LnwdB
Type 3.3Timber Joist Floor54 RwdB+Ctr(62 RwdB)
54 LnwdB
Type 3.4Timber Joist Floor49 RwdB+Ctr(59 RwdB)
59 LnwdB
Type 3.5Direct to Timber Joist51 RwdB+Ctr(63 RwdB)
55 LnwdB
Type 3.6140mm Concrete Floor52 RwdB+Ctr(57 RwdB)
40 LnwdB
Type 3.7140mm Concrete Floor52 RwdB+Ctr(57 RwdB)
57 LnwdB

Type 3.12

New Direct to Joist with Current Lathe and Plaster Coming Soon

RwdB+Ctr( RwdB)
LnwdB

ROBUST STANDARD DETAILS

Robust details are construction solutions which provide an alternative to pre-completion sound testing as a method of complying with the Building Regulations Part E (resistance to the passage of sound).

A robust detail, for Part E of the Building Regulations, is a separating wall or floor construction which has been assessed and approved by Robust Details Limited. In order to be approved, each robust detail must:

  • Be capable of consistently exceeding the performance standards given in The Building Regulations Approved Document E.
  • Be practical to construct on site.
  • Be reasonably tolerant to workmanship.

If you build using robust details, you won't have to carry out pre-completion sound testing but you do need to obtain permission from Robust Details Ltd and pay the fee for each home. Provided that the robust details are built correctly this will be accepted by all building control bodies as evidence that the homes are exempt from pre-completion testing. On completion of each separating floor or wall the builder is required to complete a compliance certificate and pass it to their building control officer. Without this certificate the building control will not approve the construction.

SOLUTIONAPPLICATIONEXPECTED PERFORMANCE
Board & Metal FrameCeiling TreatmentdB
Board & Timber BattensCeiling TreatmentdB
Board & Resilient BarsCeiling TreatmentdB

SOLUTIONAPPLICATIONEXPECTED PERFORMANCE
FFT-1 Deep Batten FloorFloor TreatmentAirborne: 54dB < DnTw+Ctr< 60dB
Impact:    35dB < L’nTw< 45dB
FFT-2 Cradle & Batten FloorFloor TreatmentAirborne: 54dB < DnTw+Ctr< 60dB
Impact:    35dB < L’nTw< 45dB
FFT-3 Standard Batten FloorFloor TreatmentAirborne: 54dB < DnTw+Ctr< 60dB
Impact:    35dB < L’nTw< 45dB
FFT-4 Platform FloorFloor TreatmentAirborne: 52dB < DnTw+Ctr< 57dB
Impact:    40dB < L’nTw< 45dB
FFT-5 Shallow Platform FloorFloor TreatmentAirborne: 50dB < DnTw+Ctr< 57dB
Impact:    40dB < L’nTw< 50dB
Screed FloorFloor TreatmentAirborne: 50dB < DnTw+Ctr< 57dB
Impact:    40dB < L’nTw< 50dB

SOLUTIONAPPLICATIONEXPECTED PERFORMANCE
Staggered MethodWall ServicesdB
Service Void MethodWall ServicesdB